We have 1 guest online| LPG Regulator |
|
In propane service, NFPA 58 requires Two-Stage regulation on all fixed piping systems that serve 1/2 psig (34,5 mbar) appliance systems (normally operated at 11-inches wc (27,4 mbar) pressure). Two-Stage regulation produces a nearly constant pressure to the appliance and can result in a more efficient LP-Gas operation for the dealer resulting in less maintenance and fewer installation call-backs. With properly selected regulators, the large internal relief valve provides 2 psig (0,14 bar) overpressure protection as required by NFPA 58.
Fisher Controls is a leading international supplier of costeffective products, services, and solutions used in the propane industry. Around the world, Fisher and its Distributors offer quality products as well as applications engineering, education programs, and after sales service. For any of the products described in this handbook, contact the Fisher Distributor near you.
Features:
|

The regulator truly is the heart of an LP-Gas installation. It must compensate for variations in tank pressure from 8 to 250 psig (0,55 to 17,2 bar) and deliver a constant outlet pressure of LP-Gas typically at 11-inches wc (27,4 mbar) to consuming appliances. The regulator must deliver this pressure despite the intermittent use of the appliances.